Bug 3072 - la consommation n'est pas assez précise dans le diagramme de câblage des serveurs : now the database contains the measured power consumption of machines and the power diagram uses it instead of the power consumption of a chassis, which is still used for an estimate in case the measured one is not available
This commit is contained in:
parent
82816e5193
commit
78d7e02285
|
@ -269,13 +269,21 @@ class PowerConfig(object):
|
|||
except TableAttrNotFound:
|
||||
pass
|
||||
|
||||
if re.match('[a-z]+.._..', machine_name):
|
||||
num_machines = 1
|
||||
match = re.match(r'(?P<cluster_name>[a-z]+)(?P<first_index>[0-9]+)_(?P<last_index>[0-9]+)', machine_name)
|
||||
if match:
|
||||
# machine_name is a group of machines such as physix80_83
|
||||
# in this case, we use a hack : the type and power consumption is based on the first machine of this group (in this example physix80)
|
||||
machine_name = '_'.join(machine_name.split('_')[0:-1])
|
||||
# machine_name = '_'.join(machine_name.split('_')[0:-1])
|
||||
print('machine_name = %s' % machine_name)
|
||||
first_index = int(match.group('first_index'))
|
||||
last_index = int(match.group('last_index'))
|
||||
machine_name = '%s%02d' % (match.group('cluster_name'), first_index)
|
||||
num_machines = last_index - first_index + 1
|
||||
|
||||
# print(machine_name)
|
||||
|
||||
# find the max power consumption of this machine
|
||||
machine_spec_id = None
|
||||
try:
|
||||
# assert machine_spec_id != '', 'non-empty value expected for machine_spec_id for machine %s' % machine_name
|
||||
|
@ -286,9 +294,23 @@ class PowerConfig(object):
|
|||
pass
|
||||
|
||||
if machine_spec_id is not None:
|
||||
power_consumption = inventory.machine_spec_id_to_power_consumption(machine_spec_id)
|
||||
if power_consumption is not None:
|
||||
machine.power_consumption = power_consumption
|
||||
measured_max_power_consumption = inventory.machine_to_power_consumption(machine_name)
|
||||
estimated_max_power_consumption = None
|
||||
chassis_power_consumption = inventory.machine_spec_id_to_power_consumption(machine_spec_id)
|
||||
if chassis_power_consumption is not None:
|
||||
estimated_max_power_consumption = chassis_power_consumption
|
||||
try:
|
||||
cpu_power_consumption = inventory.get_num_cpus(machine_name) * inventory.get_cpu_tdp(machine_name)
|
||||
estimated_max_power_consumption += cpu_power_consumption
|
||||
except TableAttrNotFound as e: # noqa: F841
|
||||
pass # could happen for machines that have no cpu (eg simpa-switch-cisco-2)
|
||||
if measured_max_power_consumption is not None:
|
||||
machine.power_consumption = num_machines * measured_max_power_consumption
|
||||
if estimated_max_power_consumption is not None:
|
||||
# assert measured_max_power_consumption > estimated_max_power_consumption, 'the estimated power consumption (%f W) of %s is too far from is measured value (%f W)' % (estimated_max_power_consumption, machine_name, measured_max_power_consumption)
|
||||
pass
|
||||
elif estimated_max_power_consumption is not None:
|
||||
machine.power_consumption = num_machines * estimated_max_power_consumption
|
||||
|
||||
def get_connection_to(self, to_plug):
|
||||
for connection in self.connections:
|
||||
|
|
12
inventory.py
12
inventory.py
|
@ -64,6 +64,14 @@ class Inventory(object):
|
|||
power_consumption = 0.0
|
||||
return power_consumption
|
||||
|
||||
def machine_to_power_consumption(self, machine_id):
|
||||
try:
|
||||
power_consumption = float(self._sql_reader.get_table_attr('machine_to_power_consumption', 'machine_id', machine_id, 'power_consumption'))
|
||||
except SimpaDbUtil.TableAttrNotFound as e: # noqa: F841 @UnusedVariable
|
||||
# some passive machines such as pdus are not detailed in the machine_spec_to_power_consumption because they don't consume power
|
||||
power_consumption = None
|
||||
return power_consumption
|
||||
|
||||
def get_plug_type_attr(self, plug_type, attr_name):
|
||||
"""
|
||||
:param str plug_type: eg 'c14'
|
||||
|
@ -161,6 +169,10 @@ class Inventory(object):
|
|||
cpu_model = self._sql_reader.get_table_attr('computer_to_cpu', 'computer_id', computer_name, 'cpu_model')
|
||||
return float(self._sql_reader.get_table_attr('cpu_specs', 'cpu_model', cpu_model, 'clock_speed'))
|
||||
|
||||
def get_cpu_tdp(self, computer_name):
|
||||
cpu_model = self._sql_reader.get_table_attr('computer_to_cpu', 'computer_id', computer_name, 'cpu_model')
|
||||
return float(self._sql_reader.get_table_attr('cpu_specs', 'cpu_model', cpu_model, 'tdp'))
|
||||
|
||||
def get_computer_dflops(self, computer_name):
|
||||
# print(computer_serial_number)
|
||||
num_cpus = int(self._sql_reader.get_table_attr('computer_to_cpu', 'computer_id', computer_name, 'num_cpu'))
|
||||
|
|